Estimated service demand load

Estimated service demand load

Determine the estimated service demand load in volt-ampres and amperes @ 240V for a residence having the following characteristics:
2500 sq ft
25 general use receptacle outlets in unfinished areas
4 small appliance branch circuits supplying the kitchen areas
1 laundry circuit
1 dedicated branch circuit supplying outside receptacles
OH door operators: 2 @ 1/2 hp, 115 V each
Sump pump: 1/2 hp, 115 V
Dishwasher: 1/3 hp pump motor, 1000 W dryer element
Garbage disposal: 1/2 hp, 115 V
Microwave hood: 8 A , 115 V
Refrigerator: 9 A, 115 V
Counter mounted cooktop: 6 kW, 230 V
Wall mounted oven: 8 kW, 230 V (supplied from same circuit as cooktop)
Air conditioning unit: 24 A, 230 V
attached are the notes I got from class regarding the chapter and the work I have done so far

Document Preview:

General illumination 2500 sq @ 3 VA= 7500
General-use 25 @ 180 VA= 4500
Small-appliance 4 @ 1500= 6000
Laundry circuit 1 @ 1500 VA= 1500
Dedicated branch 1 @ 1500 VA= 1500
OH Door 2 @ ½ hp, 115 V= 2254
Sump pump 115 x 7.2= 828
Dishwater 1000
Garbage disposal 115 x 9.8= 1127
Microwave hood 115 x 6.5= 748
Refrigerator 115 x 9= 1035
Air conditioning 230 x 24= 5520